Adaptive Neuro-Fuzzy SVC Control for Critical Clearing Time and Voltage Recovery in the Nigerian 330 kV Grid: An Ajaokuta–Benin Corridor Simulation Study
Itoro E. Udosen *
Electrical and Electronics Engineering Department, University of Uyo, Uyo, Akwa Ibom State, Nigeria.
Nseobong I. Okpura
Electrical and Electronics Engineering Department, University of Uyo, Uyo, Akwa Ibom State, Nigeria.
Kufre M. Udofia
Electrical and Electronics Engineering Department, University of Uyo, Uyo, Akwa Ibom State, Nigeria.
Akaninyene B. Obot
Electrical and Electronics Engineering Department, University of Uyo, Uyo, Akwa Ibom State, Nigeria.
*Author to whom correspondence should be addressed.
Abstract
Voltage recovery and transient rotor-angle stability are interconnected challenges in long-distance high-voltage transmission corridors. This study investigates an adaptive neuro-fuzzy inference system (ANFIS) controller for a 200 Mvar static var compensator (SVC) positioned at the midpoint of a nominal 250 km, 330 kV Ajaokuta–Benin corridor model. MATLAB/Simulink time-domain studies compared the uncompensated system with proportional-integral (PI), artificial neural network (ANN), and ANFIS-based SVC control under three-phase faults and loading levels from 80% to 120% of nominal. At Ajaokuta, the critical clearing time increased from 0.145 s without compensation to 0.195 s with PI-SVC, 0.225 s with ANN-SVC, and 0.265 s with ANFIS-SVC, corresponding to an 82.8% increase over the uncompensated case. At 120% loading, the ANFIS-SVC voltage recovery time was 1.3 s, compared with 3.2 s for PI-SVC and 5.5 s without compensation. In the nominal-load fault comparison, ANFIS-SVC reduced the reported voltage dip to 0.22 p.u., limited overshoot to 2.1%, and increased the damping ratio from 0.08 to 0.31. The simulation results indicate that neuro-fuzzy modulation of shunt reactive support can improve fault tolerance and post-fault voltage restoration in the investigated corridor model. The findings support further evaluation of adaptive SVC control using detailed network data and implementation-level testing.
Keywords: Adaptive neuro-fuzzy inference system, critical clearing time, dynamic security, Nigerian power grid, static var compensator, transient stability, voltage recovery